Ir / Ik / Ip의 정의(IEC 62271-1)

by 어흥^^* 2024. 4. 15.
728x90
반응형

 

 

1. Rated continuous current (Ir)

    - RMS value of the current the switchgear and controlgear can carry continuously for its service conditions

2.  Rated short-time withstand current (Ik)

   - RMS value of the short-circuit current that the switchgear and controlgear can carry     

     in the closed position during its rated duration(tk) under its service conditions.

      * rated duration(tk) : preferred value of rated duration - 1sec

        - interval of time for which the switchgear and controlgear can carry, in the closed position,

          a current equal to its rated short-time withstand current. 

 

3. Rated peak withstand current (Ip)

  - Peak current associated with the first major loop of the rated short-time withstand current that the switchgear and        controlgear can carry in the closed position under its service conditions

  - The rated peak withstand current is obtained by multiplying the RMS value of the rated short-time withstand

     current with a peak factor.

  - 50 Hz : 2.5 times

    60 Hz : 2.6 times

 4. Standard Current Ratings : IEC 60059 / R10 series

.

 

 